Best Power Unity/I UT3K Instalační manuál Strana 1

Procházejte online nebo si stáhněte Instalační manuál pro Nepřerušitelné zdroje napájení (UPS) Best Power Unity/I UT3K. Best Power Unity/I UT3K Installation manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 34
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
UNITY/I
TM
UT3K, UT4K, UT5K and UT8K
Single-PhaseUninterruptible Power Systems
Installation Manual
MLS-0351C-OL
Copyright 1994-1997 Best Power. All rights reserved.
å
Zobrazit stránku 0
1 2 3 4 5 6 ... 33 34

Shrnutí obsahu

Strany 1 - Installation Manual

UNITY/ITMUT3K, UT4K, UT5K and UT8KSingle-PhaseUninterruptible Power SystemsInstallation ManualMLS-0351C-OLCopyright 1994-1997 Best Power. All rights r

Strany 2 - SAVE THESE INSTRUCTIONS!

5Figure 3: External Bypass Switch DimensionsTable 5: External Bypass Switch DimensionsExternal Bypass Switch A B C D EBPE-0216 in.406 mm8 in.203 mm17

Strany 3 - August 8, 1997

6103 Finding a Location for the UPSFigure 4 shows an overview of a typical installation for a hardwired UPS.Figure 4: Typical Hardwired UPS Installati

Strany 4 - Contents

7• Provide proper UPS ventilation clearance and service clearance.• Required ventilation clearance: 4 inches (100 mm) at the rear and top.• Required s

Strany 5 - Tables and Figures

Section 200: Starting the AC InstallationThe UPS must be installed by a qualified electrician.201 Positioning the Equipment❑1. Put the UPS in place. F

Strany 6 - Introduction

9❑2. Size the UPS output overcurrent protection device (fuse or circuit breaker) per local coderequirements. Do not exceed the ratings in Table 7. See

Strany 7 - 101 Pre-Installation Check

10❑4. Determine the correct wire size for the grounding electrode conductor.• The grounding electrode conductor must be a minimum of #8 AWG (8.36 mm2)

Strany 8

Section 300: AC InstallationThe UPS must be installed by a qualified electrician.301 Removing the Covers and Knock Outs❑ 1. Remove the UPS side covers

Strany 9 - 102 Equipment Dimensions

12302 Installing the Conduit and Wiring❑1. Install the conduit and conduit adapters. Refer to the proper installation wiring diagram for yourapplicati

Strany 10

13❑4. Make the UPS terminal strip connections and all other AC wiring connections.• Refer to the proper installation wiring diagram for your applicati

Strany 11

14Figure 5: Wiring Diagram for UT3K, UT4K, UT5K, and UT8K UPSwith External Bypass Switch (L1, L2, N)• 50 or 60 Hz: 200 Input - 100/200 Output • 60 Hz:

Strany 12

IMPORTANT SAFETY INSTRUCTIONS!SAVE THESE INSTRUCTIONS!This manual contains important instructions for your UNITY/I™UPS.The installation and use of thi

Strany 13 - 201 Positioning the Equipment

15Notes for Figure 5CAUTION!The AC output circuit is considered as a separately-derived source. To ground this circuit, the installing electrician MUS

Strany 14

16Figure 6: Wiring Diagram for UT3K, UT4K, UT5K, and UT8K UPS withExternal Bypass Switch and External Input Isolation Transformer60 Hz: 208 or 480 VAC

Strany 15

17Notes for Figure 6CAUTION!The AC output circuit is considered as a separately-derived source. To ground this circuit, the installing electrician MUS

Strany 16 - Section 300: AC Installation

18Figure 7: Wiring Diagram for UT3K, UT4K, UT5K, and UT8K UPS withExternal Bypass Switch (L - N High Voltage Only)• 50 or 60 Hz: 200 Input - 200 Outpu

Strany 17 - CAUTION!

19Notes for Figure 7CAUTION!The AC output circuit is considered as a separately-derived source. To ground this circuit, the installing electrician MUS

Strany 18

20Figure 8: Wiring Diagram for UT3K, UT4K, UT5K and UT8K UPSwith Optional 380/400/415 VAC Input50 Hz: 380 or 400 or 415 Input - 220 or 230 or 240 Out

Strany 19

21Notes for Figure 8:Table 10: Recommended Input Fuse for Models with Optional 380/400/415 VACInputCAUTION!The AC output circuit is considered as a se

Strany 20

22Figure 9: UPS Output Wiring ConnectionsFind the output wiring configuration (Figure 9A - 9P) for your UPS input voltage and frequency andUPS output

Strany 21

23Notes for Figures 9A - 9KNOTE 1:Connect the UPS’ green and yellowneutral-to-ground (neutral-to-earth)wire (N-G bond) to the UPS outputterminal indic

Strany 22

24Notes for Figure 9L and 9MNOTE 1: Connect the UPS’ green and yellow neutral-to-ground (neutral-to-earth) wire (N-G bond) to the UPSoutput terminal i

Strany 23

August 8, 1997Who does not need to use this installation manual?If your UNITY/I has all of the following, you do notneed to use the installation instr

Strany 24

25Table 11: Maximum Output Current per Phase (Leg)304 Voltage and Phase CheckNOTE: If the UPS has external batteries, see the instructions that came w

Strany 25

26❑ 5. In order for the UNITY/I to provide the desired output voltage(s), you must program theOutput Voltage Reference parameter (Parameter 05).The Ou

Strany 26

27❑6. At the external bypass switch, make sure that the voltage from AC line to the bypass switch isclose to the voltage from the UPS to the loads. Us

Strany 27

28Section 400: Additional RequirementsNOTE: The remote Emergency Power Off (EPO) switch and service panel warning label describedbelow are required to

Strany 28 - Notes for Figures 9A - 9K

29Appendix: External Bypass SwitchesIf your UPS does not have output receptacles, you may have an external UPS Bypass Switch with anAC Line Disconnect

Strany 29 - Notes for Figure 9L and 9M

ContentsIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1Sec

Strany 30

Tables and FiguresTablesTable 1 UNITY/I Frequency, Voltage, and Bypass Switch Combinations . . . . . . . . . . . . . . . . .3Table 2 Best Power Ext

Strany 31

1IntroductionThis UNITY/ITMInstallation Manual is for models that do not have an input plug. A qualified electri-cian must install the AC wiring for t

Strany 32

2Section 100: Before Installing the UPS101 Pre-Installation CheckFind the following information. Use the labels on the equipment.UPS:• kW rating (see

Strany 33

3Table 1: UNITY/I Frequency, Voltage, and Bypass Switch Combinations1BBM = Break-Before-Make, MBB = Make-Before-Break. See the Appendix for more infor

Strany 34

4102 Equipment DimensionsFigure 1: UPS Dimensions Table 3: UPS DimensionsTable 4: Battery Cabinet Dimensions Figure 2: Battery CabinetBCAUPSModelH

Komentáře k této Příručce

Žádné komentáře